Xvent – Jak Poprawić Jakość Powietrza w Twoim Domu i Firmie

Heating unit ATACAMA

Ideal for heating industrial halls, warehouses, sports facilities,

workshops and smaller establishments.

Option to instal on the wall and on the ceiling
with a tilt adjustment option of +-30, 60° thanks to
the console included in the package.

In winter, it is used to heat the space to the required temperature.

In summer, it replaces air conditioning with air cooling.

nagrzewnica powietrza

Product benefits

High heat and air output

air flow up to 4700 m3 / hour, heat output 3-71 kW, horizontal air reach up to 17 m, vertical air reach up to 10 m

Quiet operation and high efficiency

Currently the quietest device on the market in its category. Significantly lower consumption.

We use only quality components

Reliable maintenance-free fans, high-quality copper exchangers, powder coating - all this allows to provide a five-year warranty

Possibility to continuously regulate the fan speed

Continuous speed control is enabled by used EC motors. We recommend using the Elementair-E MARK I controller.

When using a filter, the heat exchanger is protected against clogging

Basic description

Hotspot 4 EN
Protection with powder paint ensures excellent resistance even in aggressive environments.
Heat exchanger connection for external thread G ¾ “(max. operating conditions 120 ° C 1.6MPa). Integrated vent valves on the water inlet and outlet.
Robust mounting bracket for wall and ceiling mounting. Supplied with unit as standard. Its clever design allows the unit to be easily fitted by just one worker.
Fan with EC motor Higher performance and low operating costs. Low noise level even at higher unit power, continuously controllable fan speed from 20% to 100%.
High-quality copper heat exchanger with powder coating in two and three rows with power from 3 to 71kW
Manually adjustable lamellas allow individual adjustment of the air flow direction

Technical parameters

  ATACAMA 2ATACAMA 3ATACAMA 4
Moter typeECECECECECEC
Indicative serving area (ceiling height of 4 meters)0-3000-5000-1000
Airflowm³/h235022503000260047004400
Heat output rangekW3-324-394-385-449-5811-71
Heat exchange – rows232323
Water exchanger properties maximum operating water temperature 120 ° C; maximum operating pressure 1.6Mpa; pipe connection dimension G 3/4 “
Air reach – horizontalm131217141512
Air reach – verticalm8710886
Noise leveldB(A)42,342,151,750,352,151,6
Weight / with consolekg15 / 17,516 / 18,517 / 19,518 / 20,523 / 2625 / 28
The volume of water in the exchangerdm³1,42,11,42,123
Power supplyV/Hz1 ~ 230/50-601 ~ 230/50-601 ~ 230/50-60
Power consumptionW114117184189359379
CurrentA0,860,91,331,411,531,63
Fan rotationot/min137017901310
IP rangeIP545454
CodeATA1-2-ECV2CL-0A0ATA1-2-ECV3CL-0A0ATA1-3-ECV2CL-0A0ATA1-3-ECV3CL-0A0ATA1-4-ECV2CL-0A0ATA1-4-ECV3CL-0A0

 

Detailed technical information

Frequently asked questions and answers

EC motor power adjustment is necessary feature for setting the required performance of the equipment. This parameter is used as a basis for other parameters of the equipment, which influence the working comfort in the given area - such as air output, temperature and noise level. Electricity consumption, depending on the life cycle of the unit, is no less important of a parameter.

Heating power of the units is the most important parameter for the economical operation of heating of the building. A room thermostat or temperature sensor is required for correct functionality of temperature control. The placement of the
thermostat in the general presence zone outside of the door, window openings and sources of radiant heat at a height of approximately 1.5 m (reference point) is very important.

Air heating is one of the most dynamic heating systems. Air heating is a system where the heat energy is supplied to the heated room exclusively via the flowing hot air from the unit. The principle of functioning of the hot air unit is based on the heat transfer the water exchanger to the surrounding air. Using an axial fan, the air is distributed to the heated space. Air heating is suitable for spaces where a radiant heat source is not desirable.

Mixing or destratification is the principle of mixing the air with the result of an effective temperature distribution throughout the whole volume of space (the warmer air at the ceiling is mixed with colder air at he floor). 

Accessories

  • Controller ElementAir-E
  • Controller ElementAir-B
  • Servo-driven valve
  • Filter ATACAMA 2,3
  • Filter ATACAMA 4

Write to us